Quick answer: A room pressure VAV box keeps a room at positive or negative pressure automatically. The GSC-VAV-P room pressure VAV box keeps a room at higher or lower pressure than the adjacent area, within −75 to +75 Pa, using a Belimo VRU-M1R-BAC controller with an integrated differential pressure sensor. It suits rooms with non-critical leakage such as kitchens, restaurants and smoking rooms. Operating theatres, isolation rooms and cleanrooms are tight rooms and need a dedicated configuration. G-SORA is the official distributor of the GSC VAV-P line.
Need help choosing a room pressure VAV box, or a price? G-SORA replies the same day.

In many buildings, the direction air moves matters as much as temperature:
A standard VAV box controls temperature and airflow but does not measure room pressure, so it cannot do this job. That is why a room pressure VAV is needed.

Room pressure is set by the difference between supply air and exhaust or return air. Supply more than you extract and the room is positive; extract more than you supply and the room is negative.
Room pressure shifts when doors open, when filters load up or when fans change speed. Continuous automatic control is therefore safer than a one-off manual adjustment at commissioning.
The deciding factor is how airtight the room is. According to Belimo documentation, the VRU-M1R-BAC controller supports several application types depending on leakage:
| Room type | Control method | Standard GSC-VAV-P |
|---|---|---|
| Non-critical leakage (above 5–10% of supply airflow): kitchens, restaurants, smoking rooms | Controller acts on the supply or exhaust damper | Suitable |
| Tight rooms with low leakage | Bypass damper installed in parallel with the VAV box | Outside the standard configuration, needs separate assessment |
| Tight rooms with cascade control | Differential pressure drives a cascaded airflow controller | Outside the standard configuration, needs separate assessment |
Note: operating theatres, isolation rooms and cleanrooms are usually tight rooms. They need a bypass or cascade configuration and coordinated supply and exhaust design. The exact pressure differential is set by the design documents and project standards (for example ASHRAE 170 for healthcare facilities). The configuration for each room should be confirmed by the design consultant and GSC.
| Controller | Belimo VRU-M1R-BAC, integrated M1R differential pressure sensor, range −75…+75 Pa, no zero adjustment needed, 24 V AC/DC |
| Communication | BACnet MS/TP, Modbus RTU or MP-Bus; analog 0/2…10 V signal; set up via the Belimo Assistant app, NFC |
| Pressure setting | P′nom 5…75 Pa; switch between positive and negative pressure via the app or a BACnet/Modbus command |
| Door-open protection | Door monitoring: when the door opens, the actuator holds its position |
| Actuator | Belimo LM24A-VST, 5 Nm, 95° rotation, 120 s/90°, IP54, dampers up to about 1 m² |
| Casing | Mag Shield steel; stainless steel casing optional |
| Acoustic lining | 20–25 mm, does not support mould growth (ASTM C1338) |
| Criteria | Standard VAV box | GSC-VAV-P room pressure VAV |
|---|---|---|
| Controlled variable | Room temperature, airflow | Room pressure relative to the adjacent area |
| Sensor | Airflow sensor at the inlet | Differential pressure sensor connected to tubes in the room and the reference room |
| Controller | Belimo LMV-BAC-001 ZEM | Belimo VRU-M1R-BAC + LM24A-VST |
| Applications | Offices, hotels, retail | Kitchens, restaurants, smoking rooms, some hospital areas with non-critical leakage |
Can the GSC-VAV-P be used for negative pressure rooms?
Yes. The controller switches between positive and negative pressure via the Belimo Assistant app or a BACnet/Modbus command.
Can it be used for operating theatres or cleanrooms?
The standard configuration is not recommended. These are tight rooms that need a bypass or cascade configuration; send us your documents for a separate assessment.
Can a standard VAV box hold a pressure differential?
No. A standard VAV box does not measure room pressure.
What should I send to get a quote?