Hotline (+84) 906922412

CAV Box vs VAV Box: Key Differences and How to Choose for Each Area

A CAV box holds a fixed airflow, while a VAV box adjusts airflow to room temperature. This guide compares the two, shows which to use for each area and walks through VAV box sizing with the GSC catalogue.

Quick answer: The difference between a CAV box and a VAV box is simple: a CAV box holds one fixed airflow, while a VAV box raises or lowers airflow automatically according to room temperature. Fresh air, exhaust and zones with steady loads should use CAV. Offices, hotels and shops, where the load changes through the day, should use VAV. G-SORA is the official distributor of GSC CAV/VAV boxes in Vietnam, with stock in Ho Chi Minh City, Da Nang and Hanoi.

Not sure whether to choose CAV or VAV, which size, or what it costs? G-SORA replies the same day.

Call +84 866 016 027 Request a quote on Zalo

GSC round-duct CAV box and rectangular VAV box distributed by G-SORA

What is a CAV box and what is a VAV box?

Both are terminal units installed on the supply duct, upstream of the diffusers. Inside each one there is a damper, an airflow sensor and a controller with a built-in actuator. The only difference is the airflow value the controller follows:

  • CAV box (Constant Air Volume): the controller holds exactly one set airflow, whether the pressure in the main duct rises or falls.
  • VAV box (Variable Air Volume): the controller takes a signal from a thermostat (or a CO₂ sensor) and adjusts airflow between Vmin and Vmax to match what the room needs.

Both types are pressure independent: the airflow delivered to the room does not drift when duct pressure changes. That is what separates them from a manual volume control damper (VCD), which only fixes the blade position.

CAV box vs VAV box comparison

Criteria CAV box VAV box
Airflow Fixed at the set value Varies between Vmin and Vmax
Control signal No thermostat needed Thermostat or CO₂ sensor
AHU fan energy savings Almost none Yes, when the AHU has a variable speed drive
Equipment cost Lower Higher (adds a thermostat, can connect to BMS)
Typical areas Fresh air, toilet and kitchen exhaust, plant rooms, corridors Offices, hotels, retail, schools, hospitals

Three VAV box operating modes

According to the GSC VAV/CAV catalogue 2026, a VAV box has three modes, shown in the chart below:

Chart of the three VAV box operating modes: cooling, dead band and heating

  • Cooling: when the room is warmer than the set point, the damper opens further to let in more cool air.
  • Dead band: once the room reaches its set point, the damper holds a minimum airflow (for example 30%) so the room still gets enough fresh air.
  • Heating (optional): the damper holds a low airflow; if a reheat coil is fitted, the air is heated before it enters the room.

A CAV box has none of these modes. It only holds one airflow point, which is why the GSC catalogue states that CAV boxes are supplied without a thermostat.

CAV box or VAV box: which one to choose for each area?

Area Choose Why
Offices, hotel rooms, shops VAV Heat load changes with time and occupancy, so fan energy savings are largest
Fresh air supply per floor CAV The design fresh air rate must be held exactly
Toilet, kitchen and plant room exhaust CAV Exhaust airflow must stay steady regardless of temperature
Lobbies and corridors with steady loads CAV (or VAV if there is a BMS) The load barely changes, so VAV adds little
Rooms that must stay at positive or negative pressure Room pressure VAV (GSC-VAV-P) Controlled by room pressure, not temperature

In practice most buildings use both: VAV for conditioned zones, CAV for fresh air and exhaust. Note that VAV only saves energy when the AHU fan has a variable speed drive and slows down according to duct pressure. If the fan runs at a fixed speed, most of the benefit is lost.

How to size a VAV box: worked example from the GSC catalogue

The figures below are an illustration only; replace them with your project data. Suppose an office zone needs a maximum airflow of 2,000 m³/h and a minimum of 600 m³/h, using a rectangular VAV box.

  1. Formula: Q (m³/h) = W × H × v × 3,600, with W and H in m and v in m/s.
  2. Try size W300 × H200: Fmax in the catalogue table is 2,160 m³/h. A load of 2,000 m³/h is about 93% of Fmax, which is acceptable.
  3. The catalogue states an accuracy of ±5% between 20% and 100% of rated airflow. 20% of 2,160 is 432 m³/h, so the 600 m³/h minimum is still inside the accurate measuring range.
  4. If you try W400 × H300 (Fmax 4,320 m³/h), 20% is 864 m³/h, which is above the 600 m³/h minimum. That box is too large for the zone.

Rule of thumb: choose a size where the zone Vmax falls between 70% and 100% of Fmax and Vmin is no lower than 20% of Fmax. The result should be confirmed by the design engineer at a working static pressure of 50–250 Pa.

Specifications of GSC CAV/VAV boxes distributed by G-SORA

Three GSC air terminal lines: CAV box, VAV box and VAV-P room pressure box

  • Casing: Mag Shield steel (Zn-Al-Mg alloy coating), suited to humid and coastal climates.
  • Controller and actuator: Belimo LMV-BAC-001 ZEM, 24 V, 0–500 Pa differential pressure sensor, BACnet MS/TP or Modbus RTU communication, set up via NFC.
  • Internal acoustic lining: 20–25 mm thick, thermal conductivity 0.0343 W/m·K, does not support mould growth (ASTM C1338).
  • Size range: round duct Ø4"–16" (maximum airflow 357–6,460 m³/h); rectangular duct 200–1,000 mm per side, 580 mm long.
  • Shared casing: CAV (GSC-CAV.xx) and VAV (GSC-VAV.xx) use the same size table, so switching from CAV to VAV at the design stage hardly changes installation dimensions.

CAV box and VAV box FAQ

Does a CAV box need a thermostat?
No. A CAV box only holds a fixed airflow, so it comes without a thermostat.

Can a CAV box be converted to VAV after installation?
The dimensions follow the same size table, but you need to add a thermostat, reconfigure the controller and check the AHU fan logic. Send the case to G-SORA to check.

Can a VAV box run as a CAV box?
Yes, by setting Vmin equal to Vmax. Still, choosing the right type from the start is simpler and cheaper.

How do CAV/VAV boxes differ from a manual volume control damper (VCD)?
A VCD only fixes the blade position, so airflow still drifts when duct pressure changes. CAV/VAV boxes measure the actual airflow and compensate automatically.

Where to buy GSC CAV/VAV boxes in Vietnam

G-SORA is the official distributor of GSC VAV boxes, CAV boxes and VAV-P units, with stock in Ho Chi Minh City, Da Nang and Hanoi. Send us the airflow schedule for each zone or your BOQ, and G-SORA will recommend CAV or VAV for each area, select sizes and quote the same day.

Send your airflow schedule or BOQ for a same-day quote on GSC CAV/VAV boxes

Call +84 866 016 027 Request a quote on Zalo

See GSC Single Duct VAV Box · Download the GSC VAV/CAV catalogue 2026 (PDF)

  • 27/11/2026
(+84) 906922412 ZALO MESSENGER EMAIL BACKTOP